Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Rectifier |
Phase: | Three |
Still deciding? Get samples of US$ 25000/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
1 | Connection Group | Dyn11 |
2 | Rated capacity of primary winding | 3600kW |
3 | Rated capacity of sencondary winding | 3600kW |
4 | No load voltage: a1-b1-c1 a2-b2-c2 a3-b3-c3 a4-b4-c4 a5-b5-c5 |
400V +/-3% 480V +/-3.5% 550V +/-3% 690V +/-3% 800V +/-3% |
5 | Load voltage a1-b1-c1 a2-b2-c2 a3-b3-c3 a4-b4-c4 a5-b5-c5 |
400V +/-5% 480V +/-5% 550V +/-5% 690V +/-5% 800V +/-5% |
6 | Rated current | Input 5196A Output 3012A |
7 | Mains voltage fluctuation | < +/-5% |
8 | Working frequency | 50/60Hz |
9 | Efficiency | >97.5% (350kW resistive load) |
10 | The load cycle | Continous operation |
11 | Impedence voltage | 5%~8% |
12 | Type of transformer | Dry type |
13 | The temperature sampling | Thermistor (NTC) temperature switch |
14 | Isolation resistance | P,S,E>500MΩ DC2500V/60s |
15 | Dielectric strength | <20mA 3KVAC/60s Coil-Core N1/N2/N3/N4-N5 |
16 | Isolation grade | H(180ºC) |
17 | Allowable temperature rise | 95K (rated current, forced air cooling) |
18 | Noise | <70dB (measured with a sound level meter at 1m) |
19 | Cooling type | AF (Forced air cooling, control panel with independent control switch) |