Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Lighting |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Company founded in 2010. The company's headquarters is located in Jinhe community of Zhangmutou town in Dongguan. The practical area of the factory is about 10 thousand square meters. It sets up distribution outlets in East China, North China, northwest and other places. It is a high-tech enterprise in Dongguan. The company has more than 20 patents.
No. | Parameter | Test Terminal | Test Value | Test Condition | Standard Test Instrument |
1 | No Load Output Voltage | a-b, b-c, c-a | 400V(+/-3%) | Input: A-B, B-C, C-A 315V | Transformer Comprehensive Tester |
2 | Rated Load Voltage | a-b, b-c, c-a | 400V(+/-3%) | Input: A-B, B-C, C-A 315V | |
3 | Rated Load Power | 500KVA | |||
4 | Rated Load Current | a-b, b-c, c-a | 721.7A | Input: A-B, B-C, C-A 315V | |
5 | Overload Operation | Not overtemperature with 110% load at 45 degree C ambient temperature for 1.5 hours | |||
6 | Coil vector connection | Dyn 11 | |||
7 | Efficiency | >97.85% >98% |
With 500kW resistive load With 400kW resistive load |
||
8 | Short circuit impedance | <8.5% | |||
9 | Insulation resistance | Parallel rod to iron core | >100MΩ | 500V DC | 500V DC tramegger |
10 | Dielectric strength | Primary/Secondary to GND; Secondary-Primary-Temperature relay, temperature relay-Iron core | leak current<35mA/no arcing breakdown | 3000VAC/60S 3000VAC/60S |
Power frequency tester |
11 | Temperature rise | Hottest spot in coil | <115K | Rated full load, air forced cooling | K-type thermocouple |
12 | Noise | <70dB | At one meter distance | Noise meter | |
13 | Insulation grade | H | |||
14 | Surge current | a-b, b-c, c-a | <5 In | Output: a-b, b-c, c-a 400V | Transformer Comprehensive Tester |
15 | No load current | A B C | <3% | Input: A-B, B-C, C-A 315V | |
16 | DC bias | A B C | 50A | Input: A-B, B-C, C-A 315V | |
17 | Withstand ripple current | Estimate according to the rated current of 315V side | 5% rated current | Input: A-B, B-C, C-A 315V | |
18 | Voltage Range | Long term operating voltage range | -85%~+125% | 400V side | |
19 | Heat dissipating method | Forced cooling | No built-in fan | ||
20 | Storage temperature | -40ºC~70ºC | |||
21 | Full load operating temperature | -40ºC~55ºC,derating use above 55ºC | |||
22 | Operating humidity | Relative 0%~95%; abosolute: < 29g /m3, no condensation | |||
23 | Application of altitude | 0~4000m, rated current under 2000m, derating 1% for every 100m rise above 2000m | |||
24 | Polution prevention | Level 2 | |||
25 | Salt spray resistance rating | Salt content 0.1mg/m3 |