• 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case
  • 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case
  • 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case
  • 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case
  • 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case
  • 250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case

250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case

Application: Power, Electronic, Instrument, Lighting, Rectifier
Phase: Three
Core: Core-type Transformer
Cooling Method: Dry-type Transformer
Winding Type: Multi-winding Transformer
Certification: ISO9001, CCC
Customization:
Manufacturer/Factory & Trading Company
Gold Member Since 2021

Suppliers with verified business licenses

Guangdong, China
to see all verified strength labels (17)

Basic Info.

Model NO.
E-00043A
Usage
Rectifier Transformer, Combined Transformer, Power Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Silicon Steel Sheet
Brand
Bc Power
Supply Voltage Fluctuation
<+/-3%
Temperature Sampling
Thermistor Ntc Temperature Switch
Isolation Grade
Class H (180 C)
Connection Group
Dyn11
Rated Capacity of Primary Winding
250kw
Rated Capacity of Secondary Winding
250kw
Primary Rated Line Voltage
1140V
Secondary Rated Line Voltage
690V/400V
Efficiency
>98%
Temperature Rise
115K
Transport Package
Wooden Case
Specification
1000*800*1200 mm, weight<1200KG
Trademark
BC POWER or Customized
Origin
Dongguan City, Guangdong Province, China
Production Capacity
240-360 PCS/Year

Product Description

1. The primary side is 1 loop with 6 contactors are configured each to control the output of 220V/400V/480V/500V/540V separately.
2. Push-button switch is used to control the output of the contactor. The loop contactor interlock can only have one voltage output.
3. The equipment is equipped with temperature monitoring (winding temperature, core temperature) switching, and the fan is started to cool when the internal temperature is higher than 60 degrees Celsius, and the fan is stopped when the internal temperature is lower than 45 degrees Celsius. Alarm sound occurs when the internal winding temperature exceeds135 degrees Celsius. The transformers automatically shuts down the total input power when the temperature is greater than 150 degrees Celsius.
4. Product total weight nearly 1500KG.

Electric Characteristics
 
Item Parameter Value Remark
1 Model Number BC-E00043A  
2 Phase number Three Phase  
3 Rated Capacity 250KVA  
4 Rated Input Voltage 1140V  
5 Rated Output Voltage 1 690V  
6 Rated Output Voltage 2 400V  
7 Rated Load Voltage Percentage Deviation +/-3%  
8 Connection Group Dyn11  
9 Insulation Grade H  
10 Temperature Rise <115K Hottest spot in the coil at rated load
11 Efficiency >98% 145ºC
12 Cooling Type AN Natural air cooling
13 Rated short circuit impedance percentage (2.5+/-1)%  
14 Rated load input current 126.6A  
15 Peak excitation inrush current <10In at rated voltage
16 690V rated load output 1 current 120A  
17 400V rated load output 1 current 90A  
18 400V rated load output 2 current 32A  
19 400V rated load output 3 current 32A  
20 400V rated load output 4 current 16A  
21 230V rated load output current 16A  
22 Overload capacity 1.1In/1.1Un Ambient Temperature 25ºC
23 Measured no-load current Max 3A  
24 Operation mode Rated load  
25 Noise label <65dB 1 meter horizontal distance
26 Primary side to secondary side isolation voltage intensity <10mA, no arcing, no breakdown 3KV AC, 60S
27 Primary side to ground isolation voltage intensity <10mA, no arcing, no breakdown 3KV AC, 60S
28 Secondary side to ground isolation voltage intensity <10mA, no arcing, no breakdown 3KV AC, 60S
29 Primary side to ground insulation impedance >100MΩ 500VDC
30 Secondary side to ground insulation impedance >100MΩ 500VDC
31 Primary side to secondary side insulation impedance >100MΩ 500VDC
32 Local discharge limit N/A  
33 Cabinet protection grade  IP54  
34 Thermostat type Normally closed restorability  
35 Thermostat operating temperature 160+/-5ºC  
36 Thermostat qty 2  
37 Thermostact connection type parallel connection  
38 Iron yoke material  Non-oriented silicon steel sheet  
39 Iron yoke brand 30A150  
40 Rated flux density 1.297  
41 Saturation flux density 1.7T  
42 Primary coil material  Copper  
43 Secondary coil material Copper  
44 Primary coil section 72 mm2  
45 Secondary coil section 60 mm2  
46 Primary current density 1.75 A/mm2  
47 Secondary current density 2.0 A/mm2  
48 Primary side number of windings 148TS  
49 Secondary side number of windings 52TS/30TS  
250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case250kVA Distribution Transformer for Wind Generating with IP54 Protection Grade Case

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
27
Year of Establishment
2011-03-25